Energy consumption optimization in refrigeration plant for Danone, Kherson

Project period
09/2010
10/2011
Technologies
SIMATIC Step7, WinCC SCADA v6.2. CPU S7-414, industrial computer. Socomec DIRIS A40 electrical meter.

Customer: Johnson Controls Inc. (York) – Danone-Dnipro Milk Factory – Danone. Ukraine, Kherson.

Upgrade of SCADA for refrigeration plant with the purpose of energy consumption optimization. Connect Socomec DIRIS A40 meter via Profibus DP to CPU S7-414 for monitoring of electrical parameters. Install CP Optimizer Sabroe R717 to calculate the optimal discharge pressure setpoint. Alternative calculation of the optimal work mode of evaporative condensers according to the tables of operation parameters of compressor units and condensers. Automation of condensation heat recuperation system. See photos of Buco ice generator and Sabroe/York/Johnson Controls compressor unit.